Product

+
  • undefined

SZL package water-tube hot water boiler series

ThetechnicalparametersofSZLpackagewater-tubehotwaterboilerseries:TypeDataParametersSZL1.4-0.7/95/70-AⅡSZL2.8-0.7/95/70-AⅡRatedthermalpower(MW)1.42.8Ratedwateroutletpressure(Mpa)0.70.7Ratedoutletwatert

Description

The technical parameters of SZL package water-tube hot water boiler series:
 
Type Data Parameters SZL1.4-0.7/95/70-AⅡ SZL2.8-0.7/95/70-AⅡ
Rated thermal power(MW) 1.4 2.8
Rated water outlet pressure(Mpa) 0.7 0.7
Rated outlet water temperature ℃ 95 95
Rated inlet water temperature ℃ 70 70
Circulating water volume (m3/h) 48 96
Heating area Boiler body m2 66 94
Coal economizer m2 22 38.5
Grate effective area (m2) 4.1 5.2
Body water volume (m3) 5.2 5.5
Boiler efficiency (%) 77 77
Applicable fuel  Ⅱ grade coal
Fuel consumption (kg/h) 305 610
Max.transport size (m) 7500×2350×3350 7460×2500×3550
Max.transport weight (t) 23.5 29
Overall size after installation (m) / /
Draught fan
Type         
YX9-35-12 No.6.3C      right 0° YX9-35-12 No.8C  right 0°
Flow rate m3/h
4576~6266 8868~28830
Air pressure Pa
2860~2910 2860~3160
Motor power kw
11 22
Air blower
Type         
T4-72 No.4A right315° T4-72 No.4.5A right225°
Flow rate m3/h
3764~7226 5360~10288
Air pressure Pa
2306~1275 2582~1616
Motor power kw 5.5 7.5
Speed controllor Type  GL-5P GL-5P
Motor power kw 0.37 0.37
Slagging machine Type LXL-2 LXL-4
Motor power kw 1.1 1.1
Type of dust collector XD-2 XD-4
Feeding pump Type   JGGC2.4-128/16 JGGC4.8-120/16
Flux (m3/h) 2.4 4.8
Lift (m) 128 120
Power (kw) 2.2 3.0
Note: Due to the continuously improvement of our products , the above parameters also will update continuously. The parameters on this page are only for your reference. The listed boiler is representational product of our factory , please refer to some relevant drawings if you need some parameters of other boilers.

Inquiry